中文版 | English

JFB · D/3 type Electric Heating Cable

  • Product Description

JFB · D/3 type Three-phase Constant Wattage Parallel Connection Electric Heating Cable

1. Product Structure and Working Principle
 
 

Three parallel insulation copper wires form power generatrix. Electric heating threads are wound around the inner jacket insulation layer ln every certain distance, the heating thread is welded in turn to the three power generatrix circularly. This makes every 2 phases into acontinuous parallel connection resistance. When the generatrix is connected to 3 -phase power supply, the every parallel resistance heats at the same time This makes a continuous heating belt.

2.Product Types and Main Technical Characteristics
 
Table 2-2: Main Technical Parameters of JFB- 口 /3 Type Electric heat cable
Type


Rated Voltage


(v)


Rated
Power


(w/m)


Insulation Resistance


(MΩ /hm)


Electricity Intensity


(v/min)


Insulation Material

Highest Temp-
erature

(℃)

Explo-
sion 
Proof Label

Min.
Bending
Radius

(mm)

Highest
Maintenance Temperature of Media

(℃)

Max. 
UseLength
of Single
Power

(m)

Reinforced
JFB-30/3J 380 30 50 2750 F46 200 ExeIIT4
Common
30

Reinforced
35
120 320
JFB-40/3J 40 100 240
JFB-50/3J 50 80 190
JFB-60/3J 60 60 160
3.Product Characteristics and Applications

Besides the above characteristics the three phase heating cables have following advantages:
 
The most tolerable length of the three-phase heat cable is three times longer than the length of the single-phase heating cable of the same wattage.
 

Bigger section area of three phase heating cable can broaden heat transmitting area and thisincreases the transmitting efficiency.

 

③Three phase parallel connection heating cables are suitable forthethermal insulation of pipes with big diameters, pipe lines in nets and tanks.